Capacitor Trip Device Model CTD-4
The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power. The CTD-4 is available in 120V and 240V configurations.
| CTD-4 (120 Volt) |
| Normal Input Voltage | 120VAC |
| Max Input Voltage | 140VAC |
| Frequency | 0–400 Hz |
| Available Energy | 19 joules, ±20% @25°C |
| Normal Output Voltage | 338VDC |
| Normal Charge Time | 350ms to 90% at 60Hz/25°C |
| Capacitance | 330µF, ±20% @25°C |
| CTD-4 (240 Volt) |
| Normal Input Voltage | 240VAC |
| Max Input Voltage | 280VAC |
| Frequency | DC to 400 Hz |
| Available Energy | 57 joules |
| Normal Output Voltage | 338VDC |
| Normal Charge Time | 570ms to 90% at 25°C |
| Capacitance | 990µF, ±20% @25°C |
| Common |
| Temp Influence on Capacitor | -10% at -30°C, +5% at 60°C |
| Operating Temperature | -30°C to 60°C |
| Storage Temperature | -50°C to 80°C |
| Short Circuit Protection | Continuous |
| Mounting | Vertical or Horizontal |
| Input Surge Protection | MOV Protection to 65 joules single pulse surge |