Capacitor Trip Device Model CTD-2
The Model CTD (Capacitor Trip Devices) manufactured by Electromagnetic Industries are designed to provide a source of energy for a circuit breaker or switch to trip during a loss of normal AC or DC power.
| Normal Input Voltage | 120VAC, 125VDC |
| Max Input Voltage | 140VAC, 125VDC (Surge Protected) |
| Frequency | 0–400 Hz |
| Available Energy | 21.5 joules, ±20% @25°C |
| Normal Output Voltage | 170VDC (w/ 120VAC Input), 125VDC (w/ 125VDC Input) |
| Normal Charge Time | 440ms |
| Capacitance | 1500µF, ±20% @25°C |
| Operating Temperature | -30°C to 60°C |
| Storage Temperature | -50°C to 80°C |
| Short Circuit Protection | Continuous |
| Mounting | Vertical or Horizontal |
| Input Surge Protection | MOV Protection to 65 joules single pulse surge |